SIMATIC S7-400
Function modules
FM 452 cam controller
6/81
Siemens ST 70 · 2013
6
Overview
Very high speed electronic cam controller
Low-cost alternative to mechanical cam controllers
32 cam tracks, 16 onboard digital outputs for direct output of
actions
Incremental or synchronous-serial position feedback
Note:
We offer position measuring systems and preassembled
connecting cables for counting and positioning functions under
SIMODRIVE Sensor or Motion Connect 500.
www.siemens.com/simatic-technology
Technical specifications
6ES7 452-1AH00-0AE0
Supply voltage
24 V DC Yes
Input current
Current consumption, max. 500 mA
Encoder supply
5 V encoder supply
•5 V Yes
Output current, max.
300 mA
Cable length, max.
32 m
24 V encoder supply
24 V Yes
Output current, max.
300 mA
Cable length, max.
100 m
Digital inputs
Number/binary inputs 11
Functions Reference point switch, flying actual
value setting/length measurement,
brake release, enable track output
no. 3 to 10
Input voltage
Rated value, DC 24 V
for signal "0"
-28.8 to +5 V
for signal "1"
11 to 28.8 V
Input current
for signal "0", max.
(permissible quiescent current)
2mA
for 2-wire sensor
- for signal "1", typ. 9mA
Digital outputs
Number/binary outputs 16
Functions Cam track
Functionality/short-circuit strength
Yes
Output voltage
Rated value (DC) 24 V
for signal "1", min.
UP - 0.8 V
Output current
for signal "1" permissible range for 0
to 55 °C, max.
600 mA; with UPmax
for signal "0" residual current, max.
0.5 mA
Encoder
Connectable encoders
• Incremental encoder (symmetrical) Yes
• Incremental encoder (asymmetrical)
Yes
• Absolute encoder (SSI)
Yes
• 2-wire sensor
Yes
Encoder signals, incremental encoder
(symmetrical)
• Trace mark signals A, notA, B, notB
• Zero mark signal
N, notN
Input signal
5 V difference signal (phys. RS 422)
• Input frequency, max.
1MHz
Encoder signals, incremental encoder
(asymmetrical)
• Trace mark signals A, B
• Zero mark signal
N
Input voltage
24 V
• Input frequency, max.
50 kHz;
50 kHz for 25 m cable length;
25 kHz for 100 m cable length
Encoder signals, absolute encoder
(SSI)
Input signal 5 V difference signal (phys. RS 422)
• Data signal
DATA, notDATA
• Clock signal
CL, notCL
• Message frame length,
parameterizable
13 or 25 bit serial
• Clock frequency, max.
1MHz
• Gray code
1
• Cable length, shielded, max.
300 m; at max. 125 kHz
Galvanic isolation
Galvanic isolation digital inputs
• Galvanic isolation digital inputs No
Galvanic isolation digital outputs
• Galvanic isolation digital outputs No
Degree and class of protection
IP20 Yes
6ES7 452-1AH00-0AE0