Page 96 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02
mmmmm
Technical Reference
Status B
1 character, $0 to $F (convert to binary, e.g. scan point is in high alarm)
Status C
1 character, $0 to $F (convert to binary, e.g. scan point is not in rate or band alarm)
MT-01 Hold Message
Field Name Definition
Te mp
2 characters, $32 to $FA (convert to decimal and subtract 100, e.g. tempera-
ture = 20 °C)
Percent
5 characters, 00.00 to 9999. (e.g. current level = 85.00% of span, EEEE. = field
overflow)
End Of Message CR ($0D)
Field Name Definition
Start Of Message STX ($02)
Message Type
2 characters, 01 (indicates the SITRANS LU01 was removed from the
RUN mode)
End Of Message CR ($0D)
####
1 = low low alarm
1 = low alarm
1 = high alarm
1 = high high alarm
MSB LSB
####
1 = rate alarm 2
1 = rate alarm 1
1 = band alarm 1
1 = band alarm 2
MSB LSB
start of message message type end of message