Parameters
P819 Profile Pointer Amplitude
The amplitude (in dB above 1 μV) of the Echo Profile at the Pointer position.
P820 Algorithm
Chooses the algorithm to generate the measured value from the profile.
Use this to select the algorithm(s) the Sonic Intelligence echo selection is based on. Use
P805 Echo Confidence (page 69) to determine which algorithm gives the highest
confidence under all level conditions. If the wrong echo is processed, observe the echo
processing displays and select an alternate algorithm, either by entering the numeric
value desired, or as below:
1. Press MEASURE to display the Auxiliary Function symbol.
2. Press ARROWS to access the desired Reading display symbols.
3. Press ENTER when the required algorithm is displayed.
Values Range: 00 to 99 (view only)
Related
• P817 Profile Pointer Time
• P818 Profile Pointer Distance
• P820 Algorithm
• P821 Spike Filter
• P822 Narrow Echo Filter
• P823 Reform Echo
• P825 Echo Marker Trigger
Values
1
ALF = long range Area, Largest, and First average (general pur-
pose, solids)
2 A = long range Area only (coarse, heaped solids)
3 L = long range Largest only (liquids, open vessels)
4 F = long range First only (liquids, closed vessel)
5 AL = long range Area and Largest average (fine heaped solids)
6 AF = long range Area and First average (coarse flat solids)
7
LF = long range Largest and First average (general purpose,
liquids)
8 * bLF = short range Largest or First (general purpose)
9 bL = short range Largest only (solids and open vessel liquids)
10 bF = short range First only (closed vessel liquids)
Related
• P805 Echo Confidence
• P817 Profile Pointer Time
• P818 Profile Pointer Distance
• P819 Profile Pointer Amplitude
• P821 Spike Filter
• P822 Narrow Echo Filter
• P823 Reform Echo
• P825 Echo Marker Trigger