Page 52 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02
Parameters
To manually record a profile
Press TRANSDUCER to fire the transducer and record the echo profile into the
internal scope buffer for display.
For differential or average operation (P001 = 4 or 5), access Scope Displays (P810)
parameter to select the transducer number.
To save a manual record
Press ENTER to copy the echo profile record in the scope buffer and save it in the
selected address in the record library. The parameter value field displays the new record
information.
To display a record
Press key to enter display auxiliary mode.
Then press TRANSDUCER to copy the current echo profile into the scope buffer for
display on an oscilloscope or Dolphin Plus
To delete a record
Press CLEAR and then ENTER to delete the echo profile record in the selected
address. The value returns to - - - -.
P331 Auto Record Enable
Use to enable/disable the Auto Profile Record function.
P333 Auto Record Interval
Enter the time to elapse after an Auto Profile Record is saved before another Auto Profile
Record can be saved (subject to all other restrictions).
Auto Record ON and OFF Setpoints (P334 to P337)
Use Auto Record ON Setpoint (P334) and Auto Record OFF Setpoint (P335) to define the
boundaries within which the level must be, for the resultant Echo Profile to be considered
for an Auto Profile Record.
If ---- is displayed for either P334 or P335, Auto Profile Records are saved regardless of
current level (subject to all other restrictions).
Enter the level value in Units (P005) or percent of Span (P007) as referenced to
Empty (P006).
Values
Range: 0 to 1
0* Off
1On
Values
Range: 0.0 to 9999 (minutes)
Preset: 120