VOICE SYSTEM 4-1
INTRODUCTION The eight-channel digital evacuation FireFinder-XLS Voice system can be added to the
basic FireFinder-XLS fire alarm system. This is accomplished with the addition of the
DAC-NET Digital Audio card and its accompanying submodules (ZAC, LVM/LPB, SCM-8,
ZIC, FMT, TZC-8B) and zone-installed equipment (speakers, strobes, telephones).
The system is capable of automatically or manually signaling to its installed speaker
zone circuits (ZAC). The signal can be up to eight channels of prerecorded messages
and/or tones including up to two simultaneous channels of live paging. The tones and
prerecorded messages are configurable in the Zeus programming tool and are
available for upload to each installed DAC-NET. A maximum of 32 DAC-NET modules
can be installed in each FireFinder-XLS system. Each DAC-NET may input either its
own tone/message to a channel, or it may be programmed to use a tone/message
from another DAC-NET in the system.
Individual zone circuits (speaker, strobe, telephone) are bundled into geographic
groups during system configuration. These groups are either automatically controlled
by pre-programmed system logic, or manually controlled by the switches located on
one or more Command Stations. Paging, manual control, or monitoring of the speaker
or telephone groups can be performed from any location where an LVM/LPB micro-
phone, SCM switch control module, or PMI is installed.
EQUIPMENT The Control and Indicating equipment of a FinderFinder-XLS Voice system consists of
the following components:
LED Control Module (LCM)
Switch Control Module (SCM)
Live Voice Microphone (LVM)
Firefighters Master Telephone (FMT)
Telephone Zone Card (TZC-8B)
Person Machine Interface (PMI)
COMMAND STATIONS Each FireFinder-XLS Command Station configuration is unique. The requirements of
the project determine the modules needed to achieve the desired functionality. The
Control view of the Zeus Programming tool is used to configure the Command
stations. Each switch on the LVM, SCM and FCM may be configured for any of the
manual operations (See page 4-4).