VOICE SYSTEM 4-3
CHAPTER 4 | FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Evacuation Signal (EVAC) A steady red LED indicates that an evacuation signal (tone or message) is being sent
to the entire building or to selected areas of the building requesting that the occu-
pants evacuate. It is possible to have two different evacuation signals, EVAC 1 and
EVAC 2. EVAC 2 will be overridden by EVAC 1 to the same speaker group.
Alert Signal A flashing red LED indicates that an ALERT signal (tone or message) is being sent to
the entire building or selected areas to alert occupants. It is possible to have two
different alert signals, ALERT 1 and ALERT 2. ALERT 2 will be overridden by ALERT 1
to the same speaker group.
Manual Operation Once the first few minutes have been dealt with automatically, the voice alarm
system can be taken over manually by authorized personnel.
Manual voice operation functions such as emergency paging, evacuation or alert
signal activation, firefighters' telephone operation, multiple voice system command
center operation, as well as convenience page or background music operation are
possible at any time.
Emergency Page Emergency Page allows a live voice page from the emergency microphone to all or
selected speaker groups in the building. An optional preannouncement tone
preceeds emergency pages for a duration of time set in the Zeus programming tool.
Evacuation Signal (EVAC) EVAC sends the evacuation tone or message (predetermined in system design) to all
or selected speaker groups in the building. The EVAC signal will be overridden by an
emergency page to the same speaker group.
It is possible to have two different evacuation signals, EVAC 1 and EVAC 2. EVAC 2
will be overridden by EVAC 1 to the same speaker group.
Alert Signal Alert signal sends the alert tone or message (predetermined in system design) to all
or selected speaker groups in the building. The alert signal will be overridden by an
emergency page or an evacuation signal to the same speaker group.
It is possible to have two different alert signals, ALERT 1 and ALERT 2. ALERT 2 will
be overridden by ALERT 1 to the same speaker group.
Convenience Page Convenience Page allows a live voice page from the convenience page microphone
to all or selected speaker groups in the building. Convenience pages are a low priority
function and will be overridden by an emergency page, an evacuation or an alert
signal to the same speaker group.
Background Music Background Music sends background music from an external audio input to all or
selected speaker groups in the building. Background Music is the lowest priority and
will be overridden by an emergency page, an evacuation or alert signal and a conve-
nience page to the same speaker group.
SYSTEM PRIORITIES The priority of requests to a speaker group in the case that multiple signals (audio
channels) are requested at the same time are as follows:
1. Emergency Page (highest priority) 2. Warden‘s (Phone) Page
3. Evacuation Signal 1 (EVAC 1) 4. Evacuation Signal 2 (EVAC 2)
5. Alert Signal 1 (ALERT 1) 6. Alert Signal 2 (ALERT 2)
7. Convenience Page 8. Background Music (lowest priority)