Siemens FIREFINDER-XLS Instrukcja Szybki Start Strona 59

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 72
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 58
D
APPENDIX 7
These circuits are intended for 24 hour alarm monitoring only.
UL 1076 requires an HTSW-1 tamper switch as well as a PAL-1 printer. Only Models
HTRI-S/-D/-R may be used as security points. A COMMUNICATION FAILURE with an
HTRI device configured for SECURITY results in a SECURITY EVENT as well as a
communication trouble. When installing an HTRI device in the Zeus tool, be sure to
set the device usage to security; otherwise, the device usage defaults to fire alarm.
When setting the device address using the DPU, select the normally closed
alarm causing input.
Connect only one switch per HTRI input.
For proprietary burglary
application (UL 1076):
Use an HTSW-1 tamper switch to monitor the main enclosure.
Monitor each HTRI-S/-D/-R related to this application for 24 hours by using a
listed motion detector (to prevent tampering).
Monitoring of security points is performed at the PMI. The PMI is suitable
for installation at either the protected premises or remotely as a receiving
unit.
SECURITY POINT INSTALLATION
Przeglądanie stron 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 71 72

Komentarze do niniejszej Instrukcji

Brak uwag