Przeglądanie stron 266
Analog modules
5.20 Analog input module SM 431; AI 8 x 14 Bit (6ES7431-1KF10-0AB0)
S7-400 Automation System Module Data
Reference Manual, Edition 09/2009, A5E00850736-06
267
5.20.2 Commissioning the SM 431; AI 8 x 14 Bit
Setting the operating mode
You set the mode of operation of the SM 431; AI 8 x 14 Bit by means of measuring range
modules on the module and in
STEP 7
.
Measuring range modules
A measuring range module of the module matches two channels and one resistance channel
to each type of sensor. Reposition the measuring range modules to suit the measuring
method and range. The steps you have to perform to do this are described in detail in the
respective section.
For an overview of the settings of specific measuring methods and ranges, refer to the
corresponding table in the section "Measuring methods and measuring ranges of SM 431;
AI 8 x 14 Bit". The necessary settings are also shown on the label attached to the module.
Parameters
You will find a description of the general procedure for assigning parameters to analog
modules in the respective sections.
The table below provides an overview of configurable parameters, including defaults.
Table 5- 48 Parameters of the SM 431; AI 8 x 14 Bit
Parameters Value range Default
setting
1
Parameter
type
Scope
Diagnostics
Wire break
Yes/no No Static Channel
Measurement
Deacti-
vated
U
Voltage
4DMU Current (4-wire
sensor)
2DMU Current (2-wire
sensor)
R-4L Resistance (4-
conductor
connection)
R-3L Resistance (3-
conductor
connection)
Measuring method
RTD-4L Thermal resistor
(linear, 4-
conductor
connection)
U Static Channel