Digital modules
4.3 Assigning parameters to digital modules
S7-400 Automation System Module Data
98 Reference Manual, Edition 09/2009, A5E00850736-06
4.3.3 Parameters of digital output modules
Overview
The configurable digital output modules use a subset of the parameters and ranges of values
listed in the table below, depending on the functionality. For information on subsets
"supported" by specific digital modules, refer to the section dealing with the relevant module
beginning with section 4.7.
The defaults apply if you have not set any parameters in
STEP 7
.
Table 4- 5 Parameters of digital output modules
Parameters Value range Default
2
Parameter type Scope
Enable
Diagnostic interrupt
1
Yes/no No Dynamic Module
Destination CPU for
interrupt
1 to 4 - Static Module
Reaction to CPU STOP Substitute a
value (SV)
Keep last value
(KLV)
SV Dynamic Module
Diagnostics
Wire break
Yes/no No
Load voltage L+
missing
Yes/no No
Short-circuit to M
Yes/no No
Short-circuit to L+
Yes/no No
Fuse blown
Yes/no No
Static Channel
Set substitution value "1" Yes/no No Dynamic Channel 3
1
If you use the module in ER-1/ER-2, you must set this parameter to "No" because the interrupt lines
are not available in ER-1/ER-2.
2
Only in the CR (central rack) is it possible to start up the digital modules with the default settings
and without support from HWCONFIG.
3
Channels not selected for substitute value "1" are assigned substitute value "0".
Przeglądanie stron 97