S5 interface IM 463-2
7.5 Setting the operating modes of the IM 314
S7-400 Automation System Module Data
Reference Manual, Edition 09/2009, A5E00850736-06
369
BR 1
X3
X4
X1
X2
BR 2
S1
off
on
BR 3
4 3 2 1
4 3 2 1
4 3 2 1
Used in ER 701-2, ER 701-3
Setting the address area
The address area of the S5 I/O modules is set on the IM 314. This setting applies only for
the digital and analog I/O modules.
The address areas P, Q, IM3, and IM4 are available. Set the switch to the relevant position
to address the digital and analog I/O modules in these areas.
Table 7- 6 Settings address areas on the IM 314
I/O area address Switch position
O = OFF, 1 = ON
P area: F000 - F0FF S1: 0000 *
Q area: F100 - F1FF 0001
IM3 area: FC00 - FCFF 1100
IM4 area: FD00 - FDFF 1101
The first two switches on the left are
not relevant.
OFF
ON
* Factory state