General specifications
1.2 Electromagnetic compatibility
S7-400 Automation System Module Data
30 Reference Manual, Edition 09/2009, A5E00850736-06
Sinusoidal interference
The table below shows the EMC behavior of the S7-400 modules with regard to sinusoidal
interference.
Table 1- 4 Sinusoidal interference
Sinusoidal interference Test values Degree of
severity
HF irradiation (electromagnetic fields)
in accordance with IEC 61000-4-3
80 MHz to 1 GHz and 1.4 GHz to 2 GHz
10 V/m with 80 % amplitude modulation
at 1 kHz
In the ranges 87 MHz
to 108 MHz, 174 MHz to 230 MHz
and 470 MHz to 790 MHz: 3 V/m
2 GHz through 2,7 GHz
1 V/m with 80 % amplitude modulation
at 1 kHz
3
HF conductance on cables and cable
shields in accordance with IEC 61000-4-6
Test voltage 10 V, with 80% amplitude
modulation of 1 kHz in the 10 MHz to 80
MHz range
3
Emission of radio interference
Interference emission of electromagnetic fields in accordance with EN 55011: Limit value
class A, Group 1.
Table 1- 5 Interference emission of electromagnetic fields
Frequency band Limit
20 MHz to 230 MHz 30 dB (µV/m)Q
230 MHz to 1000 MHz 37 dB (µV/m)Q
Measured at a distance of 30 m
Emitted interference via the mains AC power supply in accordance with EN 55011: Limit
value class A, Group 1.
Table 1- 6 Interference emission via the mains AC power supply
Frequency band Limit
0.15 MHz to 0.5 MHz 79 dB (µV)Q
66 dB (µV)M
0.5 MHz to 5 MHz 73 dB (µV)Q
60 dB (µV)M
5 MHz to 30 MHz 73 dB (µV)Q
60 dB (µV)M