PROFIBUS DP master interface IM 467/IM 467 FO
8.4 Specifications
S7-400 Automation System Module Data
390 Reference Manual, Edition 09/2009, A5E00850736-06
Deviations from the DP interface integrated
in the CPU
Different SSL IDs for system diagnostics
Possibly extended SFC run times
Additional return codes for SFC 14 and SFC 15
8.4.2 Specifications of the IM 467 FO (6ES7467-5FJ00-0AB0)
Dimensions and weight
Dimensions W x H x D (mm)
Weight
25 x 290 x 210
700 g
PROFIBUS DP
Standard
PROFIBUS DP, EN 50 170
Transmission rate
9.6 Kbps to 12 Mbps, configurable in
steps (3 Mbps and 6 Mbps not
possible)
Transmission technology
FOC;
Wave length l = 660 nm 2 x duplex
sockets
Current consumption
Current consumption from the S7-400 bus (24 VDC)
The IM does not consume any current at 24 V, and it only
makes this voltage available at the MPI/DP interface.
Total current consumption of the
components connected to the DP
interfaces, with a maximum of 150
mA
PROFIBUS DP
Operating conditions
Can be used in SIMATIC S7-400, max. 4 IM 467 in
the central rack
IM 467 cannot be used with the CP 443-5
Supply voltage 5 VDC via the backplane bus
Current consumption 1.3 A
From 5 VDC
Addressing range Max. 4 KB for inputs and 4 KB for
outputs
DP master Yes
DPV 1
No
Enable/disable
No
Number of connectable I/O devices (slaves) 96
Number of connections for S7 functions for the programming
device and operator control and monitoring
32 + 1 diagnostic connection
Data volume per slave Max. 244 bytes