Industry Automation and Drive Technologies - SCE
TIA Training Document
Page 17 of 47 Module
E12
Status: 01/2010 Vision Sensor Shape Check with SIMATIC S7-300F 2PN/DP and VS120
9. Next, we drag the ’CPU 315F-2 PN/DP’ to the second slot.
The CPU’s order number and the version are provided on the front of the CPU.
( SIMATIC 300 CPU-300 CPU 315F-2 PN/DP 6ES7 315-2FH13-0AB0 V2.6)
10. When entering the CPU, the window below is displayed. In this window, do the following: assign
to the CPU 315F-2 PN/DP an ’IP Address’, specify the ’Subnet screen form’ and select the
’Ethernet’ that is already set up. Optionally, a ’Router Address’ can be selected for network-
overarching communication. Confirm your inputs with ’OK’ ( IP Address: 192.168.0.100
Subnet screen form: 255.255.255.0 Ethernet(1) Don’t use a router OK)