Parameterizing/addressing
10.3 Overview of parameters
SIPART PS2 with and without HART communications
134 Operating Instructions, 09/2007, A5E00074631-07
Parameter Function Parameter values Unit
Function of BE2 Normally open Normally closed
None OFF
Message only on -on
Move valve to position YE uP -uP
Move valve to position YA doWn -doWn
Block movement StoP -StoP
43.BIN2 2)
Partial-Stroke-Test PST -PST
Alarm function Normal Inverted
without OFF
A1 = Min, A2 = Max
A1 = Min, A2 = Min
44.AFCT 3)
A1 = Max, A2 = Max
45.A1 Trigger threshold, alarm 1 0.0 ... 10.0 ... 100 %
46.A2 Trigger threshold, alarm 2 0.0 ... 90.0 ... 100 %
Function for fault message output Normal Inverted
Fault
Fault + not automatic
4)
47. FCT 3)
Fault + not automatic + BE
4)
48. TIM Monitoring time for setting of fault message
"regulation deviation"
Auto / 0 ... 100
49. LIM Response threshold for fault message
"regulation deviation"
Auto / 0 ... 100
Preset (factory setting)
5)
no Nothing activated no
Strt Start of factory setting Strt
50.PRST
oCAY Display after pushing button for 5 sec oCAY
Activation of extended diagnostics
Off OFF
Single-level message On1
Two-level message On2
51.XDIAG
Three-level message On3