Installing option modules
5.4 Slit initiator alarm module
SIPART PS2 with and without HART communications
60 Operating Instructions, 09/2007, A5E00074631-07
5.4.3 Setting the limits of the slotted initiator alarm unit
Determining the switch status of slotted initiators
You will require a suitable display device to determine the switch status. For example, use
the initiator tester type 2 / Ex by Pepperl + Fuchs.
1. Connect the display device to the following terminals of the SIA unit:
41 and 42
51 and 52
2. Read the switch status of slotted initiators.
Setting the L1 and L2 limits
Proceed as follows to set the limits:
1. Move the actuator to the first desired mechanical position.
2. Adjust the upper actuating disc manually until the output signal at terminals 41 and 42
changes. Set a high-low or a low-high switchover as follows:
Rotate the actuating disc beyond the switching point until you reach the next switching
point.
3. Move the actuator to the second desired mechanical position.
4. Adjust the lower actuating disc manually until the output signal at terminals 51 and 52
changes. Set a high-low or a low-high switchover as follows:
Rotate the actuating disc beyond the switching point until you reach the next switching
point.
Note
The actuating discs are relatively difficult to move. This design prevents their
unintentional movement during operation. You can achieve an easier and finer
adjustment by reducing friction temporarily. Move the actuator to and fro while
simultaneously holding the actuating discs.
See also
Installing optional modules in the standard and intrinsically safe version (Page 50)