Siemens SIPART PS2 6DR50xx Instrukcje Operacyjne Strona 181

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 242
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 180
Alarm, error, and system messages
11.2 Diagnosis
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
181
11.2.3 Meaning of diagnostics values
1 STRKS - stroke number
The movements of the actuator in operation are summed up and can be read here as the
stroke number. Unit: 100% strokes, i.e. the path between 0 and 100% and back. The value is
written in a non-volatile memory every 15 minutes. The non-volatile memory can be set to
zero using the
increment button.
2 CHDIR - number of changes of direction
Every change of direction of the actuator caused in the dead zone is noted in the closed-loop
controller and added to the number of changes of direction.
The value is written in a non-volatile memory every 15 minutes. The non-volatile memory
can be set to zero using the
increment button.
3 CNT - number of fault messages
Every fault is noted in the closed-loop controller and added to the number of fault messages.
The counter can be set to zero using the
increment button.
4 A1CNT - number of alarms 1
and
5 A2CNT - number of alarms 2
The response of alarms 1 and 2 is counted using these two counters. Activation of alarms
using the "AFCT" parameter is a condition for this. The counters can be set to zero using the
increment button.
6 HOURS - operating hours
The runtime meter is incremented every hour as soon as electric auxiliary power is supplied
to the positioner.
7 WAY - determined actuator travel
This value indicates the actuator travel determined during the initialization process as per the
display at the end of an initialization process. Conditions for lift actuators: Specification of the
lever arm using the "YWAY" parameter.
8 TUP - actuating time up
9 TDOWN - actuating time down
These values indicate the actuating times determined during the initialization process. The
unit is seconds.
Przeglądanie stron 180
1 2 ... 176 177 178 179 180 181 182 183 184 185 186 ... 241 242

Komentarze do niniejszej Instrukcji

Brak uwag