Siemens SIPART PS2 6DR50xx Instrukcje Operacyjne Strona 168

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 242
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 167
Parameterizing/addressing
10.4 Description of parameters
SIPART PS2 with and without HART communications
168 Operating Instructions, 09/2007, A5E00074631-07
L1.LIMIT - limit for the number of strokes
Use this sub-parameter to set the base limit for the number of strokes. Set the base limit in a
range from "1" to "1.00E8".
The factory setting is "1.00E6".
L2.FACT1 - factor 1
Use this sub-parameter to set the factor for the formation of limit threshold 1. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "L1.LIMIT" and "L2.FACT1".
The threshold 1 fault message is displayed when the limit threshold 1 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "1.0".
L3.FACT2 - factor 2
Use this sub-parameter to set the factor for the formation of limit threshold 2. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "L1.LIMIT" and "L3.FACT2".
The threshold 2 fault message is displayed when the limit threshold 2 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "2.0".
L4.FACT3 - factor 3
Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "L1.LIMIT" and "L4.FACT3".
The threshold 3 fault message is displayed when the limit threshold 3 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "5.0".
See also
Display of diagnostics values (Page 178)
Przeglądanie stron 167
1 2 ... 163 164 165 166 167 168 169 170 171 172 173 ... 241 242

Komentarze do niniejszej Instrukcji

Brak uwag