Alarm, error, and system messages
11.1 Representation of system messages in the digital display
SIPART PS2 with and without HART communications
174 Operating Instructions, 09/2007, A5E00074631-07
11.1.2 System messages during initialization
Remarks about the tables:
nn stands for variable numeric values
Error symbol
/ (Slash): texts to the left and the right of the slash blink alternately
Messages during initialization
Line Message
Up Down
Meaning / cause Measure
P-- X Measuring range was exceeded, the
potentiometer is in the inactive zone, the
transmission ratio selectors or the effective
lever arm are not adjusted as per the
actuator travel
Switch the transmission ratio selector to
90° especially in case of part-turn
actuators
Adjust the effective lever length of linear
actuators as per the measuring range
RUN1 X Initialization was started, part 1 is active (the
direction of action is determined)
Wait
RUN2 X Initialization part 2 is active (actuator travel
check and determination of end stops)
Wait
RUN3 X Initialization part 3 is active (determination
and display of actuating times)
Wait
RUN4 X Initialization part 4 is active (determination of
the minimum controller increment length)
Wait
RUN5 X Initialization part 5 is active (optimization of
the transient response)
Wait until "FINSH" is displayed
(initialization completed successfully)
Acknowledge by pressing the operating
mode button slightly and exit the
configuration level by pressing it longer
YEND1 X The first end position can be approached
only in case of a manual initialization
Approach the first end position using the
"+" or "-" button
Acknowledge using the operating mode
button
YEND2 X The second end position can be approached
only in case of a manual initialization
Approach the second end position using
the "+" or "-" button
Acknowledge using the operating mode
button
RANGE X The end position or the measuring span is
beyond the permissible range only in case of
a manual initialization
Approach another end position using the
"+" and "-" buttons and acknowledge with
the operating mode button, or
Move the friction clutch until "ok" is
displayed, and then acknowledge with
the operating mode button, or
Terminate the initialization process by
pressing the operating mode button,
switch to the P-manual mode and correct
the actuator travel and the position
displacement sensor