Siemens SIPART PS2 6DR50xx Instrukcje Operacyjne Strona 227

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 242
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 226
Appendix
A.3 Test report (extract)
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
227
© exida.com GmbH siemens 04-12-06 r004 v1 r1.0.doc, April 11, 2005
Stephan Aschenbrenner Page 3 of 4
As the Electro-pneumatic Positioner SIPART PS2 is supposed to be a proven-in-use device, an
assessment of the hardware with additional proven-in-use demonstration for the device and its
software was carried out. The proven-in-use investigation was based on field return data
collected and analyzed by SIEMENS AG, A&D PI TQ2. This data cannot cover the process
connection. The proven-in-use justification for the process connection still needs to be done by
the end-user.
According to the requirements of IEC 61511-1 First Edition 2003-01 section 11.4.4 and the
assessment described in section 5.1 the Type B Electro-pneumatic Positioner SIPART PS2 with
a hardware fault tolerance of 0 and a SFF of 60% to < 90% are considered to be suitable for
use in SIL 2 safety functions The decision on the usage of proven-in-use devices, however, is
always with the end-user.
The following tables show how the above stated requirements are fulfilled for the worst case
configuration listed in Table 1.
Table 2: Summary for SIPART PS2 as single-acting shutdow n module – Failure rates
Failure categor y Failure rates (in FIT)
Fail Safe Detected 0
Fail Safe Undetected 919
Fail Dangerous Detected 4
Fail Dangerous Undetected 182
No Effect 93
Annunciation Undetected 1
Not part 76
MTBF = MTTF + MTTR 90 years
Table 3: Summary for SIPART PS2 as single-acting shutdow n module – IEC 61508 failure rates
sd su dd du
SFF DC
S
DC
D
0 FIT 1013 FIT 4 FIT 182 FIT 84% 0% 2%
Table 4: Summary for SIPART PS2 as single-acting shutdow n module – PF D
AV G
values
T[Proof] = 1 y ear T[Proof] = 5 y ears T[Proof] = 10 y ears
PF D
AV G
= 7,94E-0 4 PF D
AV G
= 3,96E-0 3 PF D
AV G
= 7,91E-0 3
The boxes marked in yellow ( ) mean that the calculated PFD
AVG
values are within the
allowed range for SIL 2 according to table 2 of IEC 61508-1 but do not fulfill the requirement to
not claim more than 20% of this range, i.e. to be better than or equal to 2,00E-03. The boxes
marked in green ( ) mean that the calculated PFD
AVG
values are within the allowed range for
SIL 2 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA–84.01–1996 and do fulfill
the requirement to not claim more than 20% of this range, i.e. to be better than or equal to
2,00E-03.
Przeglądanie stron 226
1 2 ... 222 223 224 225 226 227 228 229 230 231 232 ... 241 242

Komentarze do niniejszej Instrukcji

Brak uwag