SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
201
Technical data
13
13.1 General technical data
SIPART PS2 (all versions)
General data
Range of stroke (linear actuator) 3 ... 130 mm (0.12 ... 5.12") (angle of rotation of the
feedback shaft 16 ... 90°)
Angle of rotation (part-turn actuator) 30 ... 100°
Installation
On the linear actuator
Using the mounting kit 6DR4004-8V and, if required, an
additional lever arm 6DR4004-8L on the actuators as per
IEC 534-6 (NAMUR) with a fin, columns, or a plane
surface
On the part-turn actuator
Using the mounting kit 6DR4004-8D on the actuators with
fastening plane as per VDI/VDE 3845 and DIN 3337: The
required mount must be provided on the actuator-side;
shaft with groove, and M6 female thread.
Control unit
Five-point controller
Adaptive
Dead zone
dEbA = auto Adaptive or can be preset
dEbA = 0.1 ... 10 % Adaptive or can be preset
Analog-to-digital converter
Scanning time
10 ms
Resolution
≤ 0,05 %
Transmission error
≤ 0,2 %
Temperature influence
≤ 0.1 %/10 K (≤ 0.1 %/18 °F)
Cycle time
20 mA/HART device
20 ms
PA device
60 ms
FF device
60 ms (min. loop time)
Binary input BE1 (clamp 9/10; galvanically connected with
basic device)
Only usable for a dry contact; max. contact load <5 mA at
3 V
Degree of protection
1
) IP66 according to EN 60529 / NEMA 4X