Parameterizing/addressing
10.3 Overview of parameters
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
135
1)
Interpolation points appear only upon selection of 12.SFCT = "FrEE"
Normally closed
means:
Action on switch open or Low level
2)
Normally closed
means:
Action on switch closed or High level
Normal means: High level without fault
3)
Inverse means: Low level without fault
4)
"+" means: Logical OR combination
5)
Preset results in "NOINI"!
10.3.3 Overview parameters A to P
Introduction
These parameters are used to set the extended diagnostic functions of the positioner.
Note
Factory-set parameter values are printed in bold in the following table.
Note
Display
Parameters A to P and their sub-parameters are only displayed when the extended
diagnostics has been activated using parameter "XDIAG" with parameter value "On1", "On2"
or "On3".
Overview parameter A
Parameter Function Parameter values Unit
A. PST Partial stroke test with the following parameters:
A1.STPOS Starting position 0.0 ... 100.0 %
A2.STTOL Starting tolerance 0.1 ... 2.0 ... 10.0 %
A3.STEP Step height 0.1 ... 10.0 ... 100.0 %
A4.STEPD Step direction uP / do / uP do
A5.INTRV Test interval OFF / 1 ... 365 Days
A6.PSTIN Partial stroke test reference step time NOINI / (C)##.# / Fdini / rEAL s
A7.FACT1 Factor 1 0.1 ... 1.5 ... 100.0
A8.FACT2 Factor 2 0.1 ... 3.0 ... 100.0
A9.FACT3 Factor 3 0.1 ... 5.0 ... 100.0