NCK alarms
06/2009 Overview of alarms
2-153
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
17900 [Channel %1: ] Block %2 axis %3 is no machine axis
Parameters: %1 = Channel number
%2 = Block number, label
%3 = Axis name, spindle number
Definitions: At this point, the block context calls for a machine axis. This is the case with:
- G74 (reference point approach)
- G75 (fixed point approach)
If a geometry or additional axis identifier is used, then it must also be allowed as machine axis identifier
(MD10000 $MN_AXCONF_MACHAX_NAME_TAB).
Reaction: Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: Use machine axis identifier when programming.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
18100 [Channel %1: ] Block %2 invalid value assigned to FXS[]
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: The following values are valid at the present time:
0: "Deselect traverse against fixed stop"
1: "Select traverse against fixed stop" valid.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: --
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
18101 [Channel %1: ] Block %2 invalid value assigned to FXST[]
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: Only the range 0.0 - 100.0 is valid at the present time.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: --
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
18102 [Channel %1: ] Block %2 invalid value assigned to FXSW[]
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: Only positive values including zero are valid at the present time.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: --
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
18300 [Channel %1: ] Block %2 frame: fine shift not possible
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: Allocation of a fine shift to settable frames or the basic frame is not possible since MD18600
$MN_MM_FRAME_FINE_TRANS is not equal to 1.
Reaction: Interpreter stop
Interface signals are set.
Alarm display.