Digital modules
3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES7321-
7EH00-0AB0)
S7-300 Module data
102 Manual, 02/2013, A5E00105505-08
3.12.1 Parameters of SM 321; DI 16 x DC 24/125 V
Programming
The general procedure of programming digital modules is described in the chapter
Programming digital modules.
Parameters of SM 321; DI 16 x DC 24 V/125 V
The table below shows an overview of configurable parameters and their default settings for
SM 321; DI 16 x DC 24 V/125V.
The default settings apply if you have not set any parameters in STEP 7.
Table 3- 17 Parameters of SM 321; DI 16 x DC 24 V/125 V
Parameters Range of values Default Parameter type Efficiency range
Enable
Diagnostic interrupt
Hardware interrupt
Yes/No
Yes/No
No
No
dynamic
Module
Input delay/voltage type 0.1 ms (DC)
0.5 ms (DC)
3 ms (DC)
15 ms (DC)
20 ms (DC/AC)
3 ms (DC) static Module
Diagnostics
Wire break
Yes/No
No
static
Channel
Hardware interrupt trigger
Positive edge
Negative edge
Yes/No
Yes/No
No
No
dynamic
Channel
Tolerances of the programmable input delays
Table 3- 18 Tolerances of the input delays of SM 321; DI 16 x DC 24 V/125 V
Programmed input delay Tolerance
0.1 ms 80 μs to 200 μs
0.5 ms 580 μs to 700 μs
3 ms (default) 3.1 ms to 3.7 ms
15 ms 15.1 ms to 18.1 ms
20 ms 20.1 ms to 24.1 ms