Analog modules
6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0)
S7-300 Module data
462 Manual, 02/2013, A5E00105505-08
Instructions
The "Instructions" field indicates which actions the user has to personally carry out for the
currently active calibration step. Perform the actions indicated here and confirm by pressing
the "Continue" button. The module now executes the actions required for the currently active
calibration step. If this step is processed without a fault, the function proceeds to the next
calibration step.
If you want to avoid recording existing calibration values again during user calibration,
confirm the currently active calibration step by pressing the "Skip this step" button (rather
than "Continue"). In this case, the factory-set calibration value is used for the calibration step
which has been skipped (see "Comment" field).
In the last calibration step, the values determined during the course of calibration are
displayed.
23
4
1
New calibration values
Cancels the calibration function completely
Cancels the currently active calibration and returns to the calibration start screen
Confirms the determined calibration values, saves the values, and returns to the calibration
start screen
Figure 6-40 User-calibration values
You can now adopt these calibration values as the new values for this channel by pressing
the "Continue" button. The calibration values are saved retentively and the channel
calibration is complete.
If you do not want to use the displayed calibration values, you can either return to the start
screen and start a new calibration procedure by pressing the "Restart" button, or exit
calibration altogether by pressing the "Cancel" button.