Siemens Simatic S7-300 Instrukcja Obsługi Strona 56

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 55
Digital modules
3.1 Module overview
S7-300 Module data
56 Manual, 02/2013, A5E00105505-08
3.1.3 Relay output modules
Overview of properties
The table below shows the essential properties relay output modules
Table 3- 7 Relay output modules
Module
Properties
SM 322;
DO 16 x
Rel. AC 120 V
(-1HH01-)
SM 322;
DO 8 x
Rel. AC 230 V
(-1HF01-)
SM 322;
DO 8 x
Rel. AC 230 V/ 5 A
(-5HF00-)
SM 322;
DO 8 x
Rel. AC 230 V/ 5 A
(-1HF10-)
Number of outputs 16 outputs, electrically
isolated in groups of 8
8 outputs, electrically
isolated in groups of
2
8 outputs, electrically
isolated in groups of
1
8 outputs, electrically
isolated in groups of
1
Rated load voltage 24 VDC to 120 VDC,
48 VAC to 230 VAC
24 VDC to 120 VDC,
48 VAC to 230 VAC
24 VDC to 120 VDC,
24 VAC to 230 VAC
24 VDC to 120 VDC,
48 VAC to 230 VAC
Suitable for... AC/DC solenoid valves, contactors, motor starters, FHP motors and signal lamps
Supports isochronous
mode
no no no no
Programmable
diagnostics function
no no yes no
Diagnostics interrupt no no yes no
Substitution value output no no yes no
Special features -