Analog modules
6.5 Analog input module SM 331; AI 8 x 14 Bit High Speed; isochrone; (6ES7331-7HF0x-0AB0)
S7-300 Module data
Manual, 02/2013, A5E00105505-08
353
6.5.2 Programmable parameters
Introduction
For information on programming analog modules, refer to the chapter Programming analog
modules (Page 307).
Parameter
Table 6- 15 Overview of parameters for SM 331; AI 8 x 14 Bit High Speed
Parameters Range of values Default Parameter
type
Scope
Enable
Diagnostics interrupt
Process interrupt when limit
exceeded
yes/no
yes/no
no
no
dynamic
Module
Fast Mode (can only be set if the
331-7HF01 is included for
isochronous operation in the DP
slave properties)
yes/no no static Module
Process interrupt trigger
High limit
Low limit
May be restricted by the measuring range.
from 32511 to - 32512
from - 32512 to 32511
-
dynamic
Channel
Diagnostics
Group diagnostics
yes/no
no
static
Channel
group
Measurement
Measurement type
disabled
Voltage V
4DMU current (4-wire transducer)
2DMU current (2-wire transducer)
V
Measuring range
See the table
Measurement types and
ranges
± 10 V
Noise suppression
none; 400 Hz; 60 Hz; 50 Hz 50 Hz
dynamic
Channel or
channel
group