Analog modules
6.4 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF10-0AB0)
S7-300 Module data
340 Manual, 02/2013, A5E00105505-08
6.4.2 Programmable parameters
Introduction
For information on programming analog modules, refer to the chapter Programming analog
modules (Page 307).
Parameter
Table 6- 11 Overview of parameters of SM 331; AI 8 x 16 Bit
Parameters Range of values Defaults Parameter type Scope
Enable
Process interrupt when limit value
is exceeded
Process interrupt at end of cycle
Diagnostics interrupt
yes/no
yes/no
yes/no
no
no
no
dynamic
dynamic
dynamic
Module
Process interrupt trigger
High limit
Low limit
32511 to -32512
-32512 to 32511
-
-
dynamic
dynamic
Channel
Channel
Diagnostics
Group diagnostics
Line continuity check
yes/no
yes/no
no
no
static
Channel
Channel
Measurement
Module operating mode
Noise suppression
8 channels
4 channels
50 Hz
60 Hz
400 Hz
50/60/400 Hz
yes
no
50/60/400 Hz
dynamic
Module
Channel group
Smoothing none
weak
medium
strong
none dynamic Channel group
Measurement type Measuring range:
dynamic Channel group
disabled
Voltage
± 5 V
1 V to 5 V
± 10 V
± 10 V
Current (4-wire transducer)
0 mA to 20 mA
4 mA to 20 mA
± 20 mA
4 mA to 20 mA