Principles of analog modules
5.1 Representation of the values for analog input channels
S7-300 Module data
Manual, 02/2013, A5E00105505-08
275
5.1 Representation of the values for analog input channels
Measured value resolution
The resolution of the analog values may differ, based on the analog module and module
parameters. At resolutions < 15 bits, all bits identified by "x" are set to "0".
Note
This resolution does not apply to temperature values. Converted temperature values are the
result of a conversion in the analog module.
Table 5- 2 Supported analog value resolutions
Resolution
in bits (+ sign)
Units Analog value
dec hex high byte low byte
8 128 80
H
Sign 0 0 0 0 0 0 0 1 x x x x x x x
9 64 40
H
Sign 0 0 0 0 0 0 0 0 1 x x x x x x
10 32 20
H
Sign 0 0 0 0 0 0 0 0 0 1 x x x x x
11 16 10
H
Sign 0 0 0 0 0 0 0 0 0 0 1 x x x x
12 8 8
H
Sign 0 0 0 0 0 0 0 0 0 0 0 1 x x x
13 4 4
H
Sign 0 0 0 0 0 0 0 0 0 0 0 0 1 x x
14 2 2
H
Sign 0 0 0 0 0 0 0 0 0 0 0 0 0 1 x
15 1 1
H
Sign 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1