Digital modules
3.12 Digital input module SM 321; DI 16 x DC 24/125 V; with hardware and diagnostic interrupts (6ES7321-
7EH00-0AB0)
S7-300 Module data
106 Manual, 02/2013, A5E00105505-08
Hardware interrupt lost
A "Hardware interrupt lost" diagnostic interrupt is generated if a successive interrupt is
triggered at the channel previously saved to the stack and which has not yet been processed
by the CPU.
The CPU does not register any further interrupts at this channel unless it has completed
processing of the queued interrupts of the same channel.
Interrupt-triggering channels
The relevant hardware interrupt-triggering channel is logged in the OB40_POINT_ADDR
variable of the start information of OB40. The figure shows the bit assignments of DWORD 8
in the local data.
Byte Variable Data type Description
6/7 OB40_MDL_ADDR WORD B#16#0 Address of the interrupt-triggering module
starting
at 8
OB40_POINT_ADDR DWORD see the figure
below
Indication of the interrupt-triggering inputs
       
   
/% /% /% /%
/'
5HVHUYHG
(GJHFKDQJH&KDQQHO
(GJHFKDQJH&KDQQHO
(GJHFKDQJH&KDQQHO
(GJHFKDQJH&KDQQHO
(GJHFKDQJH&KDQQHO
(GJHFKDQJH&KDQQHO
(GJHFKDQJH&KDQQHO
(GJHFKDQJH&KDQQHO
%LWQR
Figure 3-8 Start Information of OB40: which event has triggered the hardware interrupt