Siemens Simatic S7-300 Instrukcja Obsługi Strona 329

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 328
Analog modules
6.3 Analog input module SM 331; AI 8 x 16 bit; (6ES7331-7NF00-0AB0)
S7-300 Module data
Manual, 02/2013, A5E00105505-08
329
6.3.2 Programmable parameters
Introduction
For information on programming analog modules, refer to the chapter Programming analog
modules (Page 307).
Parameters
Table 6- 6 Overview of the parameters of SM 331; AI 8 x 16 Bit
Parameters Range of values Default Parameter
type
Scope
Enable
Diagnostic interrupt
Hardware interrupt when
limit exceeded
yes/no
yes/no
no
no
dynamic
Module
Hardware interrupt trigger
High limit
Low limit
May be restricted by the measuring range.
from 32511 to - 32512
from - 32512 to 32511
-
dynamic
Channel
Diagnostics
Group diagnostics
with line continuity check
yes/no
yes/no
no
no
static
Channel
group
Measurement
Measurement type
disabled
Voltage V:
4DMU current (4-wire transducer)
V
Measuring range
See the table
Measurement types and ranges
± 10 V
Noise suppression
100 Hz; 60 Hz; 50 Hz; 10 Hz 50 Hz
dynamic
Channel
group