General technical data
1.1 Standards and approvals
S7-300 Module data
Manual, 02/2013, A5E00105505-08
19
Marine approval
Classification societies:
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
DNV (Det Norske Veritas)
GL (Germanischer Lloyd)
LRS (Lloyds Register of Shipping)
Class NK (Nippon Kaiji Kyokai)
Use in industrial environments
SIMATIC products are designed for industrial applications.
Table 1- 1 Use in industrial environments
Field of application Noise emission requirements Noise immunity requirements
Industry EN 61000-6-4: 2007 EN 61000-6-2: 2005
Use in residential areas
Note
The S7-300 is designed for use in industrial areas; using it in residential areas could disturb
radio and TV reception.
To operate an S7-300 in a residential area, it's RF emission must comply with Limit Value
Class B to EN 55011.
Suitable measures for achieving the required Class B radio interference level include, for
example:
S7-300 installation in grounded switch cabinets / cubicles
Use of noise filters in the supply lines