Principles of analog value processing
4.2 Wiring and connecting transducers to analog inputs
S7-300 Module data
Manual, 02/2013, A5E00105505-08
251
Note
Do not interconnect M- with M
ANA
when wiring and connecting 2-wire transducers and
resistance transducers. An equalization current develops at the interconnection of M- with
M
ANA
and corrupts the measured value. This also applies to unused inputs which are
programmed accordingly.
4.2.2 Wiring non-isolated transducers
Non-isolated transducer
Non-isolated transducers are interconnected with local ground potential. Always interconnect
M
ANA
with local ground when using non-isolated transducers.
Local conditions or interference may cause potential differences CMV (static or dynamic)
between locally distributed measuring points. If the maximum CMV value is exceeded,
interconnect the measuring points by means of equipotential conductors.
Wiring non-isolated transducer to electrically isolated AI
When connecting non-isolated transducers to electrically isolated modules, the CPU / IM 153
can be operated in grounded or ungrounded mode.
0
0ದ
0
0ದ
/
0
0
$1$
8
,62
8
&0
/
0
&38,0
/RJLF
0
$'&
0D
LQJURXQGOLQH
%DFNSODQH
EXV
1R
Q
LVRODWHG
VHQVRUV
(TXLSRWHQWLDO
ERQGLQJOLQH
Figure 4-3 Wiring non-isolated transducer to electrically isolated AI
Przeglądanie stron 250
1 2 ... 246 247 248 249 250 251 252 253 254 255 256 ... 675 676

Komentarze do niniejszej Instrukcji

Brak uwag