
NCK alarms/ISO alarms
06/2007 Overview of alarms
2-213
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
Definitions: The orientation of the workpiece-related protection zone and the orientation of the tool-related protec-
tion zone differ. If the protection zone number is negative, then this is a global protection zone.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: - Modify the protection zone definition or do not simultaneously activate protection zones that have
different orientations.
- Check machine data and modify the protection zone definition if necessary.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
18005 Channel %1 block %2 serious error in definition of NCK-specific
protection zone %3
Parameters: %1 = Channel number
%2 = Block number, label
%3 = Protection zone number
Definitions: The protection zone definition must be terminated with EXECUTE before a preprocessing stop is per-
formed. This also applies to any that are initiated implicitly such as with G74, M30, M17.
Reaction: Correction block is reorganized.
Local alarm reaction.
Interface signals are set.
Alarm display.
Remedy: Modify part program.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
18006 Channel %1 block %2 serious error in definition of channel-specific
protection zone %3
Parameters: %1 = Channel number
%2 = Block number, label
%3 = Protection zone number
Definitions: The protection zone definition must be terminated with EXECUTE before a preprocessing stop is per-
formed. This also applies to any that are initiated implicitly such as with G74, M30, M17.
Reaction: Correction block is reorganized.
Local alarm reaction.
Interface signals are set.
Alarm display.
Remedy: Modify part program.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
18100 Channel %1 block %2 invalid value assigned to FXS[]
Parameters: %1 = channel number
%2 = block number, label
Definitions: The following values are valid at the present time:
0:"Deselect travel to fixed stop"
1:"Select travel to fixed stop"
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
Komentarze do niniejszej Instrukcji