Overview of alarms 06/2007
NCK alarms/ISO alarms
2-28
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
Definitions: In the specified machine data, a number has been used several times for the configuration of an M
function.
Reaction: Mode group not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Check the specified machine data and create a unique assignment of M auxiliary function numbers.
Program Con-
tinuation:
Switch control OFF - ON.
4184 Channel %1 illegally predefined auxiliary function in %2%3, MD reset
Parameters: %1 = channel number
%2 = machine data identifier
%3 = if necessary, MD index
Definitions: In the specified machine data, a predefined auxiliary function has been illegally configured.
The value set by the user has been reset to the default value by the system.
Reaction: Mode group not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Configure a valid value in the specified machine data.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
4185 Channel %1 illegal auxiliary function configured %2 %3 %4
Parameters: %1 = channel number.
%2 = type of auxiliary function.
%3 = extension.
%4 = auxiliary function value.
Definitions: An auxiliary function has been illegally configured.
Predefined auxiliary functions cannot be reconfigured by user-defined auxiliary functions.
Reaction: Mode group not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Reconfigure the auxiliary function.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
4200 Channel %1 geometry axis %2 must not be declared a rotary axis
Parameters: %1 = channel number
%2 = axis name
Definitions: The geometry axes represent a Cartesian coordinate system and therefore the declaration of a geom-
etry axis as rotary axis leads to a definition conflict.
Reaction: NC not ready.
Mode group not ready, also effective for single axes
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.