Overview of alarms 06/2007
NCK alarms/ISO alarms
2-62
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
10704 Channel %1 block %2 protection zone monitoring is not guaranteed
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: New movements of a geometry axis which have been added could not be allowed for at the time of
block preparation. It is therefore not certain that the protection zones will not be violated. This is just
a warning message without further reactions.
Reaction: Interface signals are set.
Alarm display.
Remedy: Take other measures to ensure that the geomotry axes motion, including the additional motion, does
not violate the protection zones. (The warning comes nevertheless) or exclude additional motions.
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
10706 Channel %1 NCK protection zone %2 reached with axis %3 during
manual mode
Parameters: %1 = Channel number
%2 = Protection zone number
%3 = Axis name
Definitions: The workpiece-related NCK protection zone has been reached with the specified axis. Note that
another tool-related protection zone is still active. The workpiece-related protection zone can be tra-
versed when the PLC has issued an enable signal.
Reaction: Local alarm reaction.
Interface signals are set.
Alarm display.
Remedy: Please inform the authorized personnel/service department. Protection zone can be traversed after
enable signal from PLC.
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
10707 Channel %1 channel-specific protection zone %2 reached with axis %3
during manual mode
Parameters: %1 = Channel number
%2 = Protection zone number
%3 = Axis name
Definitions: The workpiece-related channel-specific protection zone has been reached with the specified axis.
Note that another tool-related protection zone is still active. The workpiece-related protection zone can
be traversed when the PLC has issued an enable signal.
Reaction: Local alarm reaction.
Interface signals are set.
Alarm display.
Remedy: Please inform the authorized personnel/service department. Protection zone can be traversed after
enable signal from PLC.
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
10710 Channel %1 block %2 conflict with centerless grinding
Parameters: %1 = Channel number
%2 = Spindle number
Definitions: Centerless grinding is active and a block has been processed that satisfies at least one of the following
conditions:
- G96 active and regulating spindle is master spindle.
- Regulating spindle is in interdependent grouping.
- Axes of centerless transformation overlap with an active transformation and a tool is active.
- Constant wheel peripheral speed for the regulating spindle is active.
Reaction: Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: Modify program.