Overview of alarms 06/2007
Profibus alarms
2-336
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007 Edition
Definitions: An incorrect logical base address was set for a digital or analog output, the area resides in the access
range of the PLC (process output copy, base addresses < 128).
Reaction: Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: Check your hardware configuration for modules that are not connected or are defective and replace
them.
If the error cannot be eliminated, please make a note of the error text and contact the control system
manufacturer.
Program Con-
tinuation:
Switch control OFF - ON.
380075 PROFIBUS DP: DP I/O failure bus %2 slave %1
Parameters: %1 = slave address
Definitions: Failure of a PROFIBUS slot used by the NCK for digital or analog I/O.
Reaction: Alarm display.
Remedy: Check that the PROFIBUS slave is operating correctly (all slaves must be included in the bus, green
LED)
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
380500 Profibus-DP: fault on drive %1, code %2, value %3, time %4
Parameters: %1 = axis
%2 = fault code of drive (P824)
%3 = fault value of drive (P826)
%4 = fault time of drive (P825)
Definitions: Contents of fault memory of assigned drive.
Reaction: Alarm display.
Remedy: For fault codes/fault values, refer to drive documentation.
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
380501 PROFIBUS DP: fault on bus,slave,DO-Id %1, code %2, value %3, time %4
Parameters: %1 = bus number
%2 = slave address
%3 = fault value of drive (P945)
%4 = fault time of drive (P948)
Definitions: Contents of fault memory of assigned slave.
Reaction: Alarm display.
Remedy: For fault codes/fault values, refer to drive documentation.
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
380502 PROFIBUS DP: bus %1, slave %2 configuration changed
Parameters: %1 = bus number
%2 = slave address
Definitions: The PB bus configuration has changed.
Causes:
- Initial start-up
- New PB slave detected on bus
Reaction: Interface signals are set.
Alarm display.
Remedy: Another warm start is needed to allow operating the bus with the new configuration.
Program Con-
tinuation:
Switch control OFF - ON.
380503 PROFIBUS DP: bus %1 configuration changed
Parameters: %1 = Bus number
Definitions: A new SDB2000 with a modified configuration was provided.